Solutions
/
e²ALPHA MV Switchgears
| e²ALPHA® | e²ALPHA®-2S | e²ALPHA®-G | |||||
|
|
|
||||||
| Switchgear rated voltage | 12kV | 17,5kV | 24kV | 12kV | 17,5kV | 24kV | 12kV |
| Lighting impulse test voltage (1,2/50μs) | 75/85kV | 95/110kV | 125/145kV | 75/85kV | 95/110kV | 125/145kV | 75kV |
| Power frequency test voltage (1-min.) |
28/32kV | 38/45kV | 50/60kV | 28/32kV | 38/45kV | 50/60kV | 28kV |
| Rated frequency | 50Hz | 50Hz | 50Hz | 50Hz | 50Hz | 50Hz | 50Hz |
| Rated current of busbar, incoming and coupling bays |
630-4000A | 630-2000A | 630-2500A | 630-2500A | 630-2000A | 630-2000A | 630-1250A |
| Rated current of outgoing bays | 630-4000A | 630-2000A | 630-2500A | 630-2500A | 630-2000A | 630-2000A | 630-1250A |
| Rated short-time withstand current (3s))/(1s)3) | up to 40kA | up to 31,5kA | up to 25kA | up to 31,5kA | up to 31,5kA | up to 25kA | up to 25kA |
| Internal arc resistance (1s) | up to 40kA | up to 31,5kA | up to 25kA | up to 31,5kA | up to 31,5kA | up to 25kA | up to 25kA |
| Rated peak withstand current | up to 100kA | up to 80kA | up to 63kA | up to 80kA | up to 80kA | up to 63kA | up to 63kA |
| Switchgear protection rating | IP4X/IP54 | IP4X/IP54 | IP4X/IP54 | IP4X/IP54 | IP4X/IP54 | IP4X/IP54 | IP54 |
| Accessibility of compartments | LSC2B | LSC2B | LSC2B | LSC2B | LSC2B | LSC2B | LSC2B |
| Classification of enclosures | PM | PM | PM | PM | PM | PM | PM |
| Internal arc resistance class | AFLR | AFLR | AFLR | AFLR | AFLR | AFLR | AFLR |
| Bay width | 400-950 mm | 400-950 mm | 750-950 mm | 650, 800 1100 mm |
650, 800, |
800, 1100 mm | 600, 750 mm |
| Bay height | 21001) - 23002) mm | 21001) - 22002) mm | 2300 mm | 2680 mm | 2680 mm | 3400 mm | 1800 mm |
| Bay depth | 12501)/ 13502) / 14404) mm | 12501) / 13502) mm |
14403) 4) mm | 1750 mm | 1750 mm | 2400 mm | 1480 mm |
| Maximum height of work | 1000 m | 1000 m | 1000 m | 1000 m | 1000 m | 1000 m | 1000 m |
| Maximum relative humidity at 25°C | 100% | 100% | 100% | 100% | 100% | 100% | 100% |
1) busbar current up to 1250 A (12 - 17,5 kV)
2) busbar current up to 2000 A (12 - 17,5 kV), up to 2500 A (12 kV)
3) busbar current up to 2500 A (24 kV)
4) busbar current up to 4000 A (12 kV)
5) duration of faults for switchgear e2ALPHA-G
•/o - standard/option